700 – 3000 VA |
5000/6000 VA |
Electrical Input |
Nominal Voltage |
|
120 Vac, 208 – 240 Vac |
208 – 240 Vac |
|
Voltage Range |
|
120 V: 80-144 V (without using batteries)
208/230 V: 160 – 288 V (without using batteries) |
123-208 V (without using batteries) |
|
Input Power Factor |
|
>.95, typical |
>.96 in any mode |
|
Frequency |
|
50/60 Hz, Auto-sensing |
|
Frequency Range |
|
45 – 65 Hz |
50 Hz: 47-53 Hz
60 Hz: 57-63 Hz |
Electrical Output |
On Utility Voltage
Regulation |
|
+/-3% of nominal |
|
On Battery Voltage
Regulation |
|
+/-3% of nominal |
|
Efficiency |
|
89 – 92%, depending on load |
>85% Online Mode; >90% High-efficiency Mode |
|
Frequency Regulation |
|
±3 Hz online; ± 1 Hz on battery |
±3 Hz online; ± 1 Hz on battery;
±3 Hz High-Efficiency Mode |
|
Load Crest Factor |
|
3 to 1 ratio
|
Battery |
Internal Battery type |
|
9 Ah, Sealed, lead-acid; maintenance free |
7 Ah, Sealed, lead-acid; maintenance free |
|
EBM Battery Type |
|
9 Ah, Sealed, lead-acid; maintenance free |
9 Ah, Sealed, lead-acid; maintenance free |
|
Battery Replacement |
|
Hot-swappable internal and external batteries |
|
Recharge Time |
|
<2 hrs. From complete discharge to 100% capacity at nominal line conditions |
|
Start-On-Battery |
|
Allows start of UPS without utility input |
Communications |
Serial Port |
|
RS-232 communications port standard;
optional X-slot modules available |
RS-232 and USB communications port standard;
optional X-slot modules available |
|
Communications cable |
|
6-foot communications cable included |
General |
Topology |
|
True online, double-conversion |
|
Diagnostics |
|
Full system self-test on power up |
|
UPS Bypass |
|
Automatic on Overload or UPS failure |
Environmental and Safety |
Safety Markings |
|
120 V: UL, CSA and NOM
230 V: UL, CSA, VDE, CE, S, D, N, FI, B, NOM, R
208 V: UL, CSA |
UL, cUL, VDE, CE, NOM, NYCE, GS |
|
EMC Markings |
|
FCC Class B and VCCI Class II, 3000 FCC Class A |
FCC-A, VCCI-A, BSMI-A, C-Tick, CE Compliance |
|
Surge Suppression |
|
IEEE/ANSI C62.41 Category B (formerly 587) |
ANSI C62.41 Category B3, and EN61000-4-5 Level 3 Criteria B |
|
Audible Noise |
|
<45 dBA (on utility); <50 dBA (on battery)
|
|
Ambient operating |
|
0 to 40ºC (32 to 104ºF); 0 to 25ºC (32 to 77ºF)
|
|
Heat Dissipation |
|
2066 BTU/hr. Max
|
|
Leakage Current |
|
< .6mA Typical
|
|
Relative Humidity |
|
0 to 90%, non-condensing |
5 to 90%, non-condensing |
|
REPO Port |
|
NEC Code 645-11 intent and UL requirements
|
|
Network Transient Protector |
|
In and out jack for models only or 10Base-T network cable; protection. UL497A tested |
N/A |