Has your solenoid tester ever over-heated, melted, burned out, or worse?

The new, full-featured Fluke T+PRO Electrical Tester offers all the advantages of a traditional solenoid tester, with added functionality, but none of the typical drawbacks.

The Fluke T+PRO Electrical Tester is the ideal, full-featured tester for the demanding commercial and industrial electrician.  With voltage measurement, continuity, built-in flashlights, GFCI trip capability, and Fluke’s legendary ruggedness and reliability, the tester is an excellent choice for most residential, commercial, and industrial applications.

The Fluke T+PRO Electrical Tester comes with a rotary field indicator for troubleshooting three-phase systems, resistance measurement to 9.99 KOhms, as well as a backlit LCD display for easier viewing.

The Fluke T+PRO helps electricians comply with NPFA 70E Article 110.9 (A), which states that “Test equipment … shall be rated for circuits and equipment to which they will be connected. The T+PRO Electrical Tester carries a CAT IV 600 V and CAT III 1000 V rating, appropriate for most environments where electricians work.

Applications:

  • Industrial electricians, commercial electricians, particularly those who work on low-voltage lighting.
  • Front-line electrical troubleshooting
  • AC/DC voltage measurement
  • Continuity testing
  • Testing GFCI circuits
  • Resistance measurement
  • Checking the rotation of electrical motors
  • Checking the proper set up of 3-phase systems
  • Troubleshooting low-voltage lighting

What’s Included:

  • User manual
  • Test lead wrap
  • Fluke TP2 test probes
  • 2 AAA batteries
  • Safer than traditional solenoid testers
  • 4 forms of ac/dc voltage detection: lights, beeper, vibration for added user protection and convenience and LCD display
  • Still indicates live voltage without battery power for added user protection
  • Extra-heavy-duty, replaceable test leads for added durability
  • CAT IV  600V, CAT III 1000V rated for added user protection
  • Continuity beeper, GFCI Trip, Flashlight
  • Backlit LCD display for easier viewing
  • Resistance, Rotary Field Indication and Display Hold
  • Replaceable test probes for added convenience
  • Probe storage on back for added convenience
  • Probe holder for easier testing
  • Hazardous voltage warning light for added user protection
  • Test lead strap included for better test lead management
  • AC/DC Voltage: 12 V – 600 V on LED bar, 10.2 V – 600 V on LCD
  • LCD Resolution: 0.1 V for voltages < 50 V, 1V for voltages >= 50 V Auto-off to save battery power
  • 2-year warranty
Specifications
Temperature
Operating -10 °C to 55 °C (14 °F to 131 °F)
Storage -30 °C to 60 °C (-22 °F to 140 °F)
Relative humidity
0 °C to 30 °C (32 °F to 86 °F): 90 %
30 °C to 40 °C (86 °F to 104 °F): 75 %
40 °C to 50 °C (104 °F to 122 °F): 45 %
Altitude
Operating 2,000 m (approx. 6,561.6 ft)
Storage 10,000 m (approx. 32,808.4 ft)
Battery type/life
AAA (2); 40 hours
Shock, vibration
Sinusoidal vibration per MIL-PRF-28800F for a Class 2 instrument
Safety
ISA-82.02.01 (IEC 61010-1 Mod) Second Edition, CAN/CSA-C22.2 No. 61010-1 Second Edition, IEC 61010 – 1 to 1000 V CAT III/600 V CAT IV
Compliance to NFPA 70E*
AC Bandwidth
45 Hz to 66 Hz
Maximum working voltage
1000 V ac/dc
Maximum measurable voltage
600 V ac/dc
Duty cycle
Indefinitely for voltages up to 240 V
For voltages between 240 V and 600 V the duty cycle is 30 s on / 300 s off
For voltages above 240 V the tester must connect to a voltage source only for a MAXIMUM of 30 s and then disconnect for a MINIMUM of 300 s
Voltage hazard LED
LEDs turn on at voltages > 30 V ac/dc ± 35 %
LED voltage indication levels
12 V, 24 V, 48 V, 120 V, 208 V, 240 V, 277 V, 480 V, 600 V
LEDs
LEDs turn on between 90 % and 100 % of the indicated voltage on the LED, except for the 12 V LED which turns on between 50 % and 100 %
LCD Accuracy
AC voltage ± (3 % rdg + 2 digits)
DC voltage ± (2 % rdg + 2 digits)
Resistance ± (5 % rdg + 3 digits)
LCD Resolution
0.1 V for voltages < 50 V, 1 V for voltages ≥ 50 V
0.01 kΩ for resistance measurement
GFCI Test current
100 V – 150 V @ 6 mA – 9 mA ac, 150 V – 240 V < 12 mA
Standard input test current
< 5 mA
Size (HxWxL)
1.3 in x 2.15 in x 7.6 in (3.3 cm x 5.46 cm x 19.3 cm )
Weight