Powerware 9120
The Powerware 9120 UPS provides maximum power quality and backup power protection in the 700 – 3000 VA range and is the ideal power management solution for networks, Web servers and telecommunications equipment. While offering basic surge protection and backup power, the Powerware 9120 UPS additionally offers the best UPS power protection against all nine common power quality problems.
- Isolates connected equipment from all incoming power problems to provide the highest degree of protection
- Doubles battery service life and gives you advanced warning of the end of useful battery life
- Conditions incoming power without depleting the battery to preserve battery power for complete power outages
- Prolongs backup time with Extended Battery Modules (EBMs)
- Quickly collects information on UPS status, power usage, battery backup time, and other critical parameters with an intuitive LCD screen
- Extends backup time for select equipment with Load segments
- Minimizes downtime with hot-swappable batteries
- Protects equipment connected by network or phone wiring from “back door” power surges with a Network Transient Protector
- Ensures data integrity with free Software Suite bundle including LanSafe software, PowerVision software, and NetWatch
- Easily incorporates connectivity products with an option slot to integrate into various environments and applications
- Guarantees performance with the Triple Power Warranty
- Enhances warranty coverage with optional Gold Plan
Electrical Input | Nominal Voltage | 120 Vac and 230 Vac; | |
Input Voltage Range | 120V: 80 -144 Vac 230V: 120/140/160-276 Vac |
||
Input Power Factor | >.95% | ||
Operating Frequency | 50/60 Hz, Auto-sensing | ||
Frequency Range | 45 – 65 Hz | ||
Input Protection | Fuse or circuit breaker | ||
Electrical Output | On Utility Voltage Regulation |
+/-2% of nominal | |
On Battery Voltage Regulation |
+/-3% of nominal | ||
Nominal Output Voltage |
Same as selected input voltage | ||
Output Voltage Waveform |
Sine Wave | ||
Output Voltage Distortion |
<3%THD | ||
Output protection | Electronic overload sensing, and circuit breaker protection | ||
Efficiency | Online Mode:>86%; Hi-Efficiency Mode:>90% |
||
Battery | Internal Battery type | Sealed, lead-acid; maintenance free | |
EBM Battery Type | Sealed, lead-acid; maintenance free | ||
Battery Replacement | Hot-swappable internal and external batteries | ||
Recharge Time | <4 hours to 90%capacity | ||
Start-On-Battery | Allows start of UPS without utility input | ||
Communications | User Interface | LCD status screen | |
Audible Alarms | UPS alarm conditions, including: On-Battery, Low Battery, Overload, UPS Fault |
||
Network transient Protector | In and out jack for all models. UL497A tested |
||
REPO Port | Meets NEC code 645-11 intent and UL requirements | ||
Communications | One RS232 Serial Port; One Communications Slot; One USB Port | ||
Communications cable | 6-foot communications cable included | ||
General | Topology | True online, double-conversion | |
Diagnostics | Full system self-test on power up | ||
UPS Bypass | Automatic on Overload or UPS failure <4ms | ||
Transfer Time to battery | 0 ms | ||
Overload Capacity | 125% for 10 minutes before transfer to bypass; 150% for 10 seconds before transfer to bypass |
||
Environmental and Safety | Safety Certifications | UL1778;cUL22.2 NO.107. | |
EMI Compliance | FCC Part 15, Class B (700-1500), Class A (2000-3000) 230 V, EN 50091-2 Class B (700-1500), Class A (2000-3000) |
||
Operating Temperature | 0 to 40 C (32 to 104 F) | ||
Storage Temperature | -15 to 50 C (5 to 122 F) | ||
Relative Humidity | 0%to 95%non-condensing | ||
Immunity | EEE C62.41, IEC 61000-4 -2, -3, -4, -5 |
||
Network Transient Protector | UL497A | ||
Audible Noise at 1 meter | 700-1000 VA: <45dB;1500 VA <50dB; 2000-3000 <52dB | ||
Altitude | 3000m (10,000 ft) without deteriorating |